Control Transformer

 

         Single or double phase control transformers are commonly used in machine control panels, automation panels etc  either as security step up or step down transformer, in some cases step-up and step down transformers can be produces as auto transformer for reducing the price.


        • Nominal Power
        • Isolation type or auto type
        • Input-output voltage and current values according to duty factor
        • Galvanic isolation
        • Input - Output voltage steps
        • Input-output connection materials
        • Isolation class
        • Mounting type ( horizontal - vertical ) ... etc

        OMSAN determines these technical specifications by communicating directly to the customer before designing process in order to avoid any problem.  When every detail is clear a sample transformer is produced and tested by OMSAN and submitted to the customer for the final approving before the ordering.
 


 

  GENERAL TECHNICAL SPECIFICATIONS
  STANDARDS   EN 61558-1;  EN 61558 2-2,  EN 61558 - 2-13,   CE certified
  DESIGN   Security isolation or auto type  single phase transformer
  NOMINAL POWER   25 VA ... 10 kVA
  NOMINAL INPUT VOLTAGE   < 1000 V AC
  NOMINAL OUTPUT VOLTAGE   < 500 V AC / 708 V DC
  NOMINAL FREQUENCY   50 / 60 Hz
  MAGNETIC CIRCUIT   1,8 W/kg power loss 0,50 mm lamination (0,35mm is optional)
  WINDINGS   Electrolytic copper or aluminum
  CONNECTIONS   Transformer terminal blocks, rail terminals, copper cable lugs, copper bar
  PROTECTION ( electricity, optional)   Thermistor 90 °C 1 NK contact
  PROTECTION CLASS   IP 00
  ISOLATION CLASS   1. class, upon request; B 120 °C, F 155 °C or H 180 °C
  OPERATING TEMPERATURE   Ta 40 °C / B, Ta 55 °C / F or Ta 60 °C / H
  IMPREGNATION   According to insulation class, protection against moisture, lesser sound level
  COOLING   Natural
  HUMIDITY   %90 non-condensing ( DIN 40040 )
  OPERATING ALTITUDE   0 - 2000 m
  AMBIENT TEMPERATURE   - 20 °C ..... + 55 °C (Ta 60 °C / H)
  STORING TEMPERATURE   - 20 °C ..... + 70 °C
  SPECIAL DESIGN   Special design is possible according to voltage, current and power values,

 

 





TRANSFORMER REQUEST FORM
COMPANY DATE
NAME POSITION COUNTRY
ADDRESS
PHONE FAX NO GSM
WEB E-MAIL

A) TYPE AND POWER
TYPE ISOLATION TYPE TRANSFORMER AUTO TRANSFORMER
POWER VA cos f 1 PHASE 2 PHASE 3 PHASE

B) INPUT VOLTAGE - CURRENT AND CONNECTION METHODS
  VOLT AC AMPERE STAR DELTA OTHER
INPUT

C) OUTPUT VOLTAGES - CURRENTS AND CONNECTION METHODS
  VOLT AC / DC AMPERE YILDIZ ÜÇGEN OTHER
OUTPUT 1
OUTPUT 2
OUTPUT 3
OUTPUT 4
OUTPUT 5
FREQUENCY   OPERATING TIME RESTING TIME

D) MATERIAL SPECIFICATIONS
ISOLATION CLASS OF WINDINGS B 120°C F 155°C HO-180°C H-180°C CAM ELYAF 210 °C
COPPER ALUMINUM
LAMINATION THICKNESS AND TESLA VALUES 0,50 mm 1 TESLA 1,8 W/Kg POWER LOSS 0,35 mm 1,2 TESLA 1,5 W/Kg POWER LOSS
 
TERMINAL BLOCK ROW RETMINAL SPECIAL TERMINAL RAIL TERMINAL MOTOR TERMINAL CABLE
COPPER BAR AL. BAR CU CABLE LUG AL CABLE LUG    
   

E) WITHIN METAL ENCLOSURE
DIMENSIONS ( cm ) WIDTH HEIGHT DEEP
ACCESORIES CIRCUIT BREAKER TMS SWITCH WHEEL
CONNECTIONS OUT ENC. IN ENC. CABLE TERMINAL PLUG BAR CAB. LUG RAIL TER. OTHER
INPUT CONNECTION
OUTPUT CONNECTION
DISPLAY VOLTMETER AMPERMETER SIGNAL LAMBS
PLACE - COOLING OUTDOOR INDOOR NATURAL FAN COIL

 

                                                                   
                               

                                                                  

 

CONTROL TRANSFORMERS (E-I LAMINATION)
HORIZONTAL MOUNTING TYPE DIMENSIONS
   PRODUCT CODE   POWER (VA) MODEL A (mm) B (mm) C (mm) D (mm) E (mm) F (mm) G (mm) H (mm) WEIGHT (kg)
  OM KP TR 25 25 A 60 50 69 51 5 9 52 64 0,77
  OM KP TR 35 35 A-B 76 65 82 65 5 9 42 58 0,98
  OM KP TR 50 50 A 84 71 88 72 4,5 10 48 64 1,37
  OM KP TR 75 75 A 84 71 88 72 4,5 10 58 74 1,9
  OM KP TR 100 100 A 84 71 88 72 4,5 10 68 84 2,25
  OM KP TR 160 160 A 108 78 112 92 5 7,5 67 83 3
  OM KP TR 200 200 A-B-C 120 85 122 102 7 10 68 82 3,65
  OM KP TR 250 250 A-B-C 120 85 122 102 7 10 78 92 4,5
  OM KP TR 300 300 B-C-D 120 85 122 102 7 10 98 112 6
  OM KP TR 400 400 B-C-D 150 104 147 127 9 13 80 100 6,6
  OM KP TR 500 500 B-C-D 150 104 147 127 9 13 85 105 7,35
  OM KP TR 600 600 C-D 150 104 147 127 9 13 100 120 9,2
  OM KP TR 750 750 B-D 171 142 165 145 9 13 88 118 10,4
  OM KP TR 1000 1000 B-D 171 142 165 145 9 13 108 138 13,5
  OM KP TR 1500 1500 D 192 140 183 163 9 16 118 144 17
  OM KP TR 1750 1750 D 192 140 183 163 9 16 123 150 18,2
  OM KP TR 2000 2000 D 192 140 183 163 9 16 143 170 22,3
  OM KP TR 2500 2500 D 192 140 183 163 9 16 163 190 26,1
  OM KP TR 3000 3000 D 192 140 183 163 9 16 183 210 30,8
  OM KP TR 4000 4000 D 250 180 231 211 11 22 148 178 37,2
  OM KP TR 5000 5000 D 250 180 231 211 11 22 168 198 44,5
  OM KP TR 6000 6000 D 250 180 231 211 11 22 208 238 58,5
  OM KP TR 8000 8000 D 300 193 273 253 13 20 164 210 60
  OM KP TR 10000 10000 D 300 193 273 253 13 20 184 230 71
** DIMENSIONS OF TRANSFORMERS MANUFACTURED UPON REQUEST MAY BE DIFFERENT THAN WRITTEN IN THIS TABLE.

 

Copyright © 2013 Omsan - All rights reserved.
Group of Companies: Omsan Trafo Haydar Cömert
                            Omsan Grup Enerji İnşaat Ltd. Şti.
       
Corporate
Documents
Catalogs
Contact Information
About Us
Vision & Mission
Quality Policy
Central
Ş.Teğmen Kalmaz Cad. No:8/4
Ulus / ANKARA
Telephone: +90 312 311 71 25- 311 91 09
Fax: +90 0312 309 16 77
Factory
1480.(Eski 706) Sok. NO:44
İvedik OSB / ANKARA
Telephone: +90 312 394 55 54 - 394 55 53
Fax: +90 312 394 55 52